LUXOMAT® PD4 Master 2C

Occupancy detector LUXOMAT® PD4-M-2C-SM, master with circular detection area,
surface mounted.

Occupancy detector, master with 360° detection area, surface mounted
Energy saving potentials of up to 80%
Automatic reading of the actual light level
Switching for all types of light fixtures by high performance relay
Switching of other loads e.g. HVAC by potential free relay of the detector
Compact design, power supply and control unit in one cabinet
Semi-automatic and full automatic mode

Technical data

Power voltage: 230 V~ + 6% /-10%
Detection area: circular 360°
Range (Ø) H = 2.5 m / T = 18°C in m:
- seated 6.4
- walking across 24.0
- walking towards 8.0
Adjustments manual or with remote control IR-PD (accessory)
Installation in parallel mode Master / Slave
Light control: Mixed light
(daylight and artificial light)
Power consumption: < 1 W
Channel 1(Control the lighting)
Switching power:
2300 W, cosf = 1; 1150 W, cosf = 0.5
Time settings: Impulse or 15 sec. - 30 min.;
Light sensor: 10 - 2000 Lux
Channel 2 (Control HVAC)
Switching power:
dry contact type NO, 230 V, 3 A, cosf = 1
Time settings: impulse or 5 - 120 min.
Time delay: 5 min. for follow-up time > 15 min.
Dimensions: Ø 106 x H 69 mm
Protection degree / class: IP54 / II / CE
Ambient temperature: -25°C to +50°C